    modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630

    This topic has been deleted. Only users with topic management privileges can see it.
    • F
      fefaul @Homoran last edited by

      @homoran Ich brauch nicht unbedingt 2 Instanzen, hatte das nur gemacht weil die Settings verschiedenen waren und es nicht geklappt hat. (Und Ich keine Ahnung habe..)

      Habe das gerade einmal alles in einer Instanz gemacht. Ergebnisse gibt es aber erst Morgen, die Sonne scheint gerade nicht 😉

      Aber an den Instanzen kann es eigentlich nicht liegen. Hatte auch schon jeweils eine der Instanzen deaktiviert und die Fehler gab es trotzdem. Als ob da auf der Leitung irgendwas stört. 😐

      Homoran 1 Reply Last reply Reply Quote 0
      • Homoran
        Homoran Global Moderator Administrators @fefaul last edited by

        @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

        Als ob da auf der Leitung irgendwas stört.

        wäre auch möglich, aber was meinst du mit

        @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

        weil die Settings verschiedenen waren

        Alle Geräte eines Buss3s müssen schon die selben Settings haben.

        und das
        Screenshot_20230620-171550_Firefox.jpg
        scheinst du ja beachtet zu haben.

        F 1 Reply Last reply Reply Quote 0
        • F
          fefaul @Homoran last edited by

          @homoran
          Ja, die sind auf jeden Fall auf daisy-chained und nicht im Stern, die gleichen Einstellungen haben Sie auch. Ich hatte für den SDM630 "use aliases" aktiviert, aber anscheinend funktioniert das für den Kaco nicht. Ich habe das gerade mal rausgenommen.

          Aktueller Stand, den SDM630 kann ich aktuell auslesen. Die Register für den WR nicht, da der gerade aus ist.

          Ich erhalte jetzt im Log folgende Fehler, unterdrücken lässt sich das nicht oder? Das kommt daher, dass er den WR gerade nicht erreichen kann. Ist halt nur nervig im Log.

          modbus.0
          2024-03-20 21:50:38.662 warn Poll error count: 1 code: {"err":"timeout","timeout":6000}
          modbus.0
          2024-03-20 21:50:38.662 error Client in error state.
          modbus.0
          2024-03-20 21:50:38.662 error Request timed out.
          modbus.0
          2024-03-20 21:50:38.661 warn Error: undefined

          DANKE schonmal für die tolle Unterstützung hier. Hoffe das es dann Morgen funktioniert.

          Homoran 1 Reply Last reply Reply Quote 0
          • Homoran
            Homoran Global Moderator Administrators @fefaul last edited by

            @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

            Ich habe das gerade mal rausgenommen.

            dann sollten die Register jetzt so aussehen
            Screenshot_20240320-215542_Firefox.jpg

            und nicht mehr so

            Screenshot_20240320-215615_Firefox.jpg

            @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

            Das kommt daher, dass er den WR gerade nicht erreichen kann. Ist halt nur nervig im Log.

            ist ja noch brauchbar.
            mir war ein SDM72 im Bus ausgefallen, da lief der ganze Bus nicht mehr

            @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

            unterdrücken lässt sich das nicht oder?

            sag mir wenn du weisst wie 😁

            F 1 Reply Last reply Reply Quote 0
            • F
              fefaul @Homoran last edited by

              @homoran said in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

              @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

              Ich habe das gerade mal rausgenommen.

              dann sollten die Register jetzt so aussehen

              Korrekt.

              Er liest die Werte jetzt über die einen Instanz aus. Leider sind die Fehler und Verbindungsabbrüche wieder da 😞 Ich hab auch irgendwie keine Idee mehr woran das liegen kann. Wie gesagt, sobald nur eines der beiden Geräte am Bus hängt ist alles bestens 😕

              Vielleicht besorg Ich mir einfach einen zweiten Konverter und schaue ob es dann zuverlässig funktioniert. Ist zwar nicht optimal aber naja.

              Homoran 1 Reply Last reply Reply Quote 0
              • Homoran
                Homoran Global Moderator Administrators @fefaul last edited by

                @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                Vielleicht besorg Ich mir einfach einen zweiten Konverter und schaue ob es dann zuverlässig funktioniert.

                dann mach aber zwei Busse draus.

                @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                Ist zwar nicht optimal aber naja.

                musste ich für die Wärmepumpe auch machen.

                wie sieht eigentlich "der Fehler" im log aus?

                F 1 Reply Last reply Reply Quote 0
                • F
                  fefaul @Homoran last edited by

                  @homoran said in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                  @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                  Vielleicht besorg Ich mir einfach einen zweiten Konverter und schaue ob es dann zuverlässig funktioniert.

                  dann mach aber zwei Busse draus.

                  Ja definitiv, das war der Plan.

                  @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                  Ist zwar nicht optimal aber naja.

                  musste ich für die Wärmepumpe auch machen.

                  wie sieht eigentlich "der Fehler" im log aus?

                  2024-03-21 08:16:43.815 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 8. Received 12
                  2024-03-21 08:16:44.030 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 0. Received 4
                  2024-03-21 08:16:44.030 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 0. Received 8
                  2024-03-21 08:16:44.031 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 0. Received 12
                  2024-03-21 08:16:44.073 - warn: modbus.0 (53124) Poll error count: 1 code: "ReadHoldingRegisters: Invalid FC 4"
                  2024-03-21 08:16:44.155 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 20
                  2024-03-21 08:16:44.155 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 24
                  2024-03-21 08:16:44.155 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 28
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 32
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 36
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 40
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 48
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 52
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 68
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 72
                  2024-03-21 08:16:44.156 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 76
                  2024-03-21 08:16:44.443 - warn: modbus.0 (53124) Poll error count: 1 code: "ReadInputRegisters: Invalid FC 3"
                  2024-03-21 08:16:44.494 - warn: modbus.0 (53124) Poll error count: 2 code: "ReadHoldingRegisters: Invalid FC 4"
                  2024-03-21 08:16:48.313 - warn: modbus.0 (53124) Poll error count: 3 code: "App Timeout"
                  2024-03-21 08:17:43.565 - warn: modbus.0 (53124) Error in handler for 4: RangeError [ERR_OUT_OF_RANGE]: The value of "offset" is out of range. It must be >= 0 and <= 3. Received 4
                  2024-03-21 08:17:43.813 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 8. Received 12
                  2024-03-21 08:17:43.864 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 8. Received 12
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 20
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 24
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 28
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 32
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 36
                  2024-03-21 08:17:44.055 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 40
                  2024-03-21 08:17:44.056 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 48
                  2024-03-21 08:17:44.056 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 52
                  2024-03-21 08:17:44.056 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 68
                  2024-03-21 08:17:44.056 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 72
                  2024-03-21 08:17:44.056 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 12. Received 76
                  2024-03-21 08:17:45.087 - error: modbus.0 (53124) Can not set value: The value of "offset" is out of range. It must be >= 0 and <= 8. Received 12
                  2024-03-21 08:17:45.554 - warn: modbus.0 (53124) Poll error count: 1 code: "ReadHoldingRegisters: Invalid FC 4"
                  2024-03-21 08:17:45.684 - warn: modbus.0 (53124) Poll error count: 1 code: "ReadHoldingRegisters: Invalid FC 4"
                  2024-03-21 08:17:48.354 - warn: modbus.0 (53124) Poll error count: 2 code: "App Timeout"
                  2024-03-21 08:17:53.565 - warn: modbus.0 (53124) Error in handler for 4: RangeError [ERR_OUT_OF_RANGE]: The value of "offset" is out of range. It must be >= 0 and <= 3. Received 4
                  2024-03-21 08:17:56.894 - warn: modbus.0 (53124) Poll error count: 1 code: "App Timeout"
                  2024-03-21 08:18:29.763 - warn: modbus.0 (53124) Error: undefined
                  2024-03-21 08:18:29.763 - error: modbus.0 (53124) Request timed out.
                  2024-03-21 08:18:29.763 - error: modbus.0 (53124) Client in error state.
                  2024-03-21 08:18:29.763 - warn: modbus.0 (53124) Poll error count: 1 code: {"err":"timeout","timeout":6000}
                  2024-03-21 08:18:30.092 - warn: modbus.0 (53124) Poll error count: 2 code: "App Timeout"
                  2024-03-21 08:18:30.153 - warn: modbus.0 (53124) Poll error count: 3 code: "App Timeout"
                  2024-03-21 08:18:32.933 - warn: modbus.0 (53124) Poll error count: 1 code: "App Timeout"
                  2024-03-21 08:30:00.024 - info: host.iobroker instance system.adapter.ical.0 started with pid 53154
                  2024-03-21 08:30:00.727 - info: ical.0 (53154) starting. Version 1.13.3 in /opt/iobroker/node_modules/iobroker.ical, node: v18.19.1, js-controller: 5.0.19
                  2024-03-21 08:30:01.180 - info: ical.0 (53154) processing URL: muell2024 https://www.awsas.de/pickups/ics.php?namen=Stadt%20L%FCtzen%20-%20Starsiedel&locationid=a11f25f2-eaa7-4b88-bf59-2257b9137797&jahre=2024&fractions=40001,40002,40003,40004
                  2024-03-21 08:30:01.245 - info: trashschedule.0 (13339) Setting "actionNeeded" flag for type.restabfalltonne.actionNeeded to true (???)
                  2024-03-21 08:30:01.257 - warn: trashschedule.0 (13339) no events matches type "Wertstofftonne" with match "Gelbe Tonne"
                  2024-03-21 08:30:06.212 - info: ical.0 (53154) Terminated (NO_ERROR): Without reason
                  2024-03-21 08:30:06.724 - info: host.iobroker instance system.adapter.ical.0 terminated with code 0 (NO_ERROR)
                  
                  Homoran 1 Reply Last reply Reply Quote 0
                  • Homoran
                    Homoran Global Moderator Administrators @fefaul last edited by

                    @fefaul Was machst du da?

                    @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                    Can not set value

                    willst du Werte schreiben?

                    @fefaul sagte in modbus Verbindungsabbrüche - KACO Blueplanet NX3 & SDM630:

                    The value of "offset" is out of range

                    was für einen Offset hast du wo konfiguriert?

                    F 1 Reply Last reply Reply Quote 0
                    • F
                      fefaul @Homoran last edited by fefaul

                      @homoran
                      Ich möchte keine Werte schreiben und einen Offset habe ich auch nicht wissentlich konfiguriert.

                      Anbei mal die Konfig der modbus instanz. Vielleicht erkennst du ja einen Fehler.

                      2024-03-21 09_01_02-Window.png
                      2024-03-21 08_57_00-Window.png 2024-03-21 08_56_45-Window.png 2024-03-21 08_56_06-Window.png

                      Homoran 1 Reply Last reply Reply Quote 0
                      • Homoran
                        Homoran Global Moderator Administrators @fefaul last edited by Homoran

                        @fefaul du hast tcp? nicht rtu?

                        das hab ich wohl übersehen.
                        Da kann ich dir bei dem Konverter nicht helfen.

                        F 1 Reply Last reply Reply Quote 0
                        • F
                          fefaul @Homoran last edited by

                          Hallo zusammen,

                          Ich möchte noch mitteilen, dass das Problem jetzt behoben ist.

                          Ich hab einen neuen Konverter bestellt (selbes Modell / Herstellt) und jetzt funktioniert alles bestens! Anscheinend hatte der Konverter oder die Software (jetzt ist eine andere FW installiert) einen Fehler. An der Verkabelung habe Ich nichts geändert, immer noch alle Geräte an einem Kabel und 1 Koverter.

                          Hier der Vollständigkeit halber noch die Einstellungen der Instanz:

                          24ad42d4-1122-457a-b2dd-cd3c49c13398-image.png

                          Vom Konverter (Waveshare RS485->ETH)
                          f253b184-c704-4517-bb5e-7b3395bb4a17-image.png

                          Die Einstellungen für die Register lade Ich im Github hoch, falls Sie jemand benötigt: https://github.com/ioBroker/modbus-templates

                          Danke an @Homoran für die Hilfestellungen!

                          1 Reply Last reply Reply Quote 0
                          • First post
                            Last post

                          Support us

                          ioBroker
                          Community Adapters
                          Donate

                          870
                          Online

                          31.7k
                          Users

                          79.8k
                          Topics

                          1.3m
                          Posts

                          3
                          18
                          565
                          Loading More Posts
                          • Oldest to Newest
                          • Newest to Oldest
                          • Most Votes
                          Reply
                          • Reply as topic
                          Log in to reply
                          Community
                          Impressum | Datenschutz-Bestimmungen | Nutzungsbedingungen
                          The ioBroker Community 2014-2023
                          logo