    • Axel Koeneke
      Axel Koeneke @amnesia106 last edited by

      @amnesia106 Ich nutzte zwar einen Lesekopf mit USB am PI, aber evtl. helfen dir meine Parameter.
      Die sehen bei dir am Kopf anderes aus.
      44fd6bbc-97af-44d8-afc5-7c8665f6d7e6-image.png
      VG
      Axel

      1 Reply Last reply Reply Quote 0
      • apollon77
        apollon77 @klassisch last edited by

        @klassisch Ohje dann graut mir schon vor meinem anstehenden Zählertausch 🙂

        Als ich 2017 meine Solaranlage bekommen hab war das EnBW Solarplus und die kamen mit nem Zähler an der nicht in meinen bisherigen Schrank gepasst hat (da war vorher ein eHZ drin). Also haben die alles umgebaut und ich hab jetzt einen eigenen Zählerschrank im "hoch-aber-schmal" Design wo der Zähler und nochmal sicherungen und das "Strommessteil meiner - jetzt - Senec drin ist.
        Jetzt ist SolarPlus geschichte und ich bei Senec ... heisst jetzt kommen demnächst die Stadtwerke und werden den Zähler tauschen ... Ich warte quasi täglich drauf das die sich melden und dann bin ich. Gespannt was ich kriege und was die zu dem neuen Zählerschrank sagen 🙂

        K Homoran 2 Replies Last reply Reply Quote 0
        • K
          klassisch Most Active @apollon77 last edited by

          [OT - neue Zählerwelt]
          @apollon77 sagte in Adapter "smartmeter":

          Also haben die alles umgebaut und ich hab jetzt einen eigenen Zählerschrank im "hoch-aber-schmal" Design wo der Zähler und nochmal sicherungen und das "Strommessteil meiner - jetzt - Senec drin ist.

          Wie die Stadtwerke KA als grundzuständiger Meßstellenbetreiber das handhaben weiss ich leider nicht. Und deren Site scheint auch nicht aktuell zu sein, https://www.stadtwerke-karlsruhe.de/de/pk/dienstleistungen/smart-meter.php . Die sprechen noch von Freiwilligkeit für EEG Anlagen. Das stimmt ja so nicht mehr >7kWp oder >6kWh Verbrauch ist heute die Rechtsgrundlage für iMSys.
          Wenn der Zähler schon moderner ist und mit dem iMSys nachgerüstet werden kann, ist alles gut. Wenn ein neuer Zähler mit iMSys kommt, weiß ich nicht, ob die Info Schnittstelle noch bedient wird. Im FNN Lastenheft für iMSys steht dazu nichts. Also nicht garantiert.
          Meine mME ist ein Landis & Gyr E320-AM1D.A3A.A0-S1B-S3 und der war schon vorbereitet als Basis für iMSys zu dienen

          Jetzt ist SolarPlus geschichte und ich bei Senec ... heisst jetzt kommen demnächst die Stadtwerke und werden den Zähler tauschen ... Ich warte quasi täglich drauf das die sich melden und dann bin ich. Gespannt was ich kriege und was die zu dem neuen Zählerschrank sagen 🙂

          Wenn da mittlerweile ein großer Zähler mit Dreipunktbefestigung drin ist, sollte es maximal mit einem Zählertausch erledigt sein. Im besseren Fall reicht auch ein Aufrüstung wie bei mir. Frontplatte weg, GW eingeclipst, Stecker angeschlossen, Frotcover wieder drauf - fertig. Ohne Stromunterbrechung.

          Aber §14a EnWG sieht ja die Steuerbarkeit von Verbrauchern und Erzeugern durch den Netzbetreiber vor. Technische Details noch nicht genau bekannt, wahrscheinlich auf Basis von EEBus und mit EMS oder HEMS. ABER: Die vom Netzbetreiber vorgegebenen Limitationen dürfen vom Endverbraucher nicht beeinflußt oder verändert werden. Das könnte dazu führen, daß einige Hersteller von Wechselrichtern, Wallboxen, Wärmepumpen etc ihre APIs "dicht" machen oder zumindest ausdünnen. Das wäre zwar nicht die beste Lösung, aber die mit der sie die sicherlich erforderliche Zertifizierung am einfachsten und schnellsten erreichen.
          Und wir hätten das Nachsehen.

          1 Reply Last reply Reply Quote 1
          • Homoran
            Homoran Global Moderator Administrators @apollon77 last edited by

            @apollon77 sagte in Adapter "smartmeter":

            und ich hab jetzt einen eigenen Zählerschrank im "hoch-aber-schmal" Design wo der Zähler und nochmal sicherungen und das "Strommessteil meiner - jetzt - Senec drin ist

            und so etwas ist heute angeblich nicht mehr zulässig.
            Hatte ich auch und noch massig Platz drin.

            Da mussten beide Schränke gegen einen großen getauscht werden.

            Außerdem musste ich auch dieses ominöse APZ Feld haben, ist jetzt Vorschrift.

            K 1 Reply Last reply Reply Quote 1
            • apollon77
              apollon77 last edited by

              Danke Ihr zwei, ich berichte 🙂

              1 Reply Last reply Reply Quote 1
              • K
                klassisch Most Active @Homoran last edited by

                [OT-Zaehlerschrank]
                @homoran sagte in Adapter "smartmeter":

                und so etwas ist heute angeblich nicht mehr zulässig.
                Hatte ich auch und noch massig Platz drin.

                Da mussten beide Schränke gegen einen großen getauscht werden.

                Außerdem musste ich auch dieses ominöse APZ Feld haben, ist jetzt Vorschrift.

                Ja, das hat mich leider auch teuer getroffen. In einer Übergangszeit durfte man einen kleineren Schrank mit APZ Feld aussen "anflanschen". Das wurde dann untersagt und ein komplett neuer Schrank gefordert. Aber das ist ja in vielen Altbauten gar nicht möglich. Und schon gar nicht kurzfristig und widerstandsarm.
                Ich habe aber die Hoffnung, daß das beim Zählertausch derzeit nicht so eng gesehen wird. Die Netzbetreiber haben jetzt richtig Druck, einen Überblick über ihre Netze zu bekommen. Da werden viele Netzbetreiber iMSys als günstige, informationsreiche und schnelle Lösung wählen. Und solange ein Dreipunktzähler reinpasst, gibt es auch eine technische Möglichkeit das Thema "unblutig" zu handhaben. Da man derzeit das APZ Feld defür nicht mehr benötigt, können die mal alle Augen zudrücken.
                Wenn ich Netzbetreiber wäre, würde ich das genau so machen. Hauptsache der Spion ist kostengünstig und schnell eingebaut und man bekommt schnell den geforderten Überblick über die Netzlast. Bloß keinen Vorgang eröffnen und möglichst jedem (Rechts-)Streit aus dem Wege gehen.

                Wir beide hatten halt (wieder mal) Pech.

                1 Reply Last reply Reply Quote 0
                • hru
                  hru last edited by hru

                  Hallo zusammen,
                  ich habe den Adapter installiert und bekomme auch direkt Daten. Super, vielen Dank.
                  Gibt es eine Erklärung, was die einzelnen Attribute bedeuten?
                  (z.B. smartmeter.0.1-0:36_7_0__255, 1-0:56_7_0__255.value, smartmeter.0.1-0:76_7_0__255)

                  ok, habe es herausgefunden;-)
                  cfb2a928-bb2f-44ec-9409-eed8207a175d-image.png

                  Danke und Gruß
                  Hartmut

                  K 1 Reply Last reply Reply Quote 1
                  • K
                    klassisch Most Active @hru last edited by

                    @hru Glückwunsch, der Zähler gibt aber recht viel aus. Da ist der Meßstellenbetreiber aber "spendabel". Normalerweise gibts nur die Energiewerte und das Register 16 als Momentanleistung.
                    Hoffentlich kein Holley oder Logarex Zähler.

                    hru 1 Reply Last reply Reply Quote 0
                    • hru
                      hru @klassisch last edited by

                      @klassisch Der Screenshot ist irgendwo aus dem Netz, wo die Attribute erklärt werden (OBIS).

                      Ich verwende nur die folgenden Werte:

                      • smartmeter.1.1-0:16_7_0__255

                      • smartmeter.1.1-0:1_8_0__255

                      • smartmeter.1.1-0:2_8_0__255

                      Gruß Hartmut

                      1 Reply Last reply Reply Quote 1
                      • S
                        silgri last edited by silgri

                        Ich sollte bei meinem ISKRA 175 auch die Leistung der einzelnen Phasen L1, L2 und L3 haben.
                        Die Werte werden im Moment aber nicht als Objekte ausgegeben. Gibt es dazu eine Lösung? Oder stellt der ISKRA 175 diese an der Schnittstelle gar nicht zur Verfügung?

                        Homoran K F 3 Replies Last reply Reply Quote 0
                        • Homoran
                          Homoran Global Moderator Administrators @silgri last edited by Homoran

                          @silgri sagte in Adapter "smartmeter":

                          Ich sollte bei meinem ISKRA 175 auch die Leistung der einzelnen Phasen L1, L2 und L3 haben.

                          wer sagt das?

                          1 Reply Last reply Reply Quote 0
                          • S
                            silgri last edited by

                            Korrektur: Der Zähler ist ein MT176, wo gibt es denn eine Liste der SML-Werte, die er ausspuckt? Liest der Adapter automatisch alle Werte?

                            1 Reply Last reply Reply Quote 0
                            • K
                              klassisch Most Active @silgri last edited by

                              @silgri sagte in Adapter "smartmeter":

                              Ich sollte bei meinem ISKRA 175 auch die Leistung der einzelnen Phasen L1, L2 und L3 haben.

                              Intern hat der alles. Was er rausgibt entscheidet dann der Meßstellenbetreiber. Und die sind meist "datengeizig" und geben nur raus, wozu sie laut FNN verpflichtet sind: Energiewerte und Momentanleistung.
                              Der Adapter kann nur das verwerten, was gesendet wird. Beeinflussen kann man das nicht, die Schnittstelle ist unidirektional. "Et kütt wie et kütt." Leider 😞

                              1 Reply Last reply Reply Quote 0
                              • k3flo
                                k3flo last edited by

                                Hallo,

                                ich versuche seit 3 Tagen smartmeter mit einem Hichi USB an einem ISKRA MT681 zum Laufen zu bekommen.
                                Ich bekomme im Log eine Nachricht, die immer länger wird, die ich aber nicht interpretieren kann. Kann hier jemand beurteilen was mir der Zähler/smartmeter mir damit sagen will?

                                Lesekopf: Hichi v1.1 USB
                                RaspberryPi 4 mit Raspberry Pi OS Lite
                                IOBroker neuste Version (erst letztes Wochenden aufgesetzt)
                                smartmeter settings: Datenabfrageintervall 1s, rest default

                                Log:

                                2024-06-10 20:29:37.057 - info: host.9a instance system.adapter.smartmeter.0 started with pid 1111
                                2024-06-10 20:29:38.571 - debug: smartmeter.0 (1111) Redis Objects: Use Redis connection: 127.0.0.1:9001
                                2024-06-10 20:29:38.603 - debug: smartmeter.0 (1111) Objects client ready ... initialize now
                                2024-06-10 20:29:38.606 - debug: smartmeter.0 (1111) Objects create System PubSub Client
                                2024-06-10 20:29:38.608 - debug: smartmeter.0 (1111) Objects create User PubSub Client
                                2024-06-10 20:29:38.630 - debug: smartmeter.0 (1111) Objects client initialize lua scripts
                                2024-06-10 20:29:38.639 - debug: smartmeter.0 (1111) Objects connected to redis: 127.0.0.1:9001
                                2024-06-10 20:29:38.657 - debug: smartmeter.0 (1111) Redis States: Use Redis connection: 127.0.0.1:9000
                                2024-06-10 20:29:38.666 - debug: smartmeter.0 (1111) States create System PubSub Client
                                2024-06-10 20:29:38.667 - debug: smartmeter.0 (1111) States create User PubSub Client
                                2024-06-10 20:29:38.680 - debug: smartmeter.0 (1111) States connected to redis: 127.0.0.1:9000
                                2024-06-10 20:29:38.714 - debug: smartmeter.0 (1111) Plugin sentry Initialize Plugin (enabled=true)
                                2024-06-10 20:29:39.131 - info: smartmeter.0 (1111) starting. Version 3.4.0 in /opt/iobroker/node_modules/iobroker.smartmeter, node: v20.14.0, js-controller: 5.0.19
                                2024-06-10 20:29:39.172 - debug: smartmeter.0 (1111) SmartmeterObis options: {"debug":2,"protocol":"SmlProtocol","transport":"SerialResponseTransport","requestInterval":"1","anotherQueryDelay":"1000","transportSerialPort":"/dev/serial/by-id/usb-Silicon_Labs_CP2102_USB_to_UART_Bridge_Controller_0059-if00-port0","transportSerialBaudrate":null,"transportSerialMessageTimeout":null,"protocolSmlIgnoreInvalidCRC":false}
                                2024-06-10 20:29:39.175 - debug: smartmeter.0 (1111) CREATE SERIALPORT: 9600 8 1 none
                                2024-06-10 20:29:39.198 - debug: smartmeter.0 (1111) SERIALPORT OPEN
                                2024-06-10 20:29:39.206 - debug: smartmeter.0 (1111) ADD NEW DATA (0 + NEW 15)
                                2024-06-10 20:29:39.208 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000" -> null
                                2024-06-10 20:29:39.209 - debug: smartmeter.0 (1111) SET MESSAGE TIMEOUT TIMER: 120000
                                2024-06-10 20:29:39.214 - debug: smartmeter.0 (1111) ADD NEW DATA (15 + NEW 8)
                                2024-06-10 20:29:39.215 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e600" -> null
                                2024-06-10 20:29:39.220 - debug: smartmeter.0 (1111) ADD NEW DATA (23 + NEW 7)
                                2024-06-10 20:29:39.221 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000" -> null
                                2024-06-10 20:29:39.224 - debug: smartmeter.0 (1111) ADD NEW DATA (30 + NEW 5)
                                2024-06-10 20:29:39.224 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c" -> null
                                2024-06-10 20:29:39.229 - debug: smartmeter.0 (1111) ADD NEW DATA (35 + NEW 3)
                                2024-06-10 20:29:39.229 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe10" -> null
                                2024-06-10 20:29:39.234 - debug: smartmeter.0 (1111) ADD NEW DATA (38 + NEW 5)
                                2024-06-10 20:29:39.235 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe100000000000" -> null
                                2024-06-10 20:29:39.237 - debug: smartmeter.0 (1111) ADD NEW DATA (43 + NEW 5)
                                2024-06-10 20:29:39.238 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066" -> null
                                2024-06-10 20:29:39.239 - debug: smartmeter.0 (1111) connected set to false
                                2024-06-10 20:29:39.242 - debug: smartmeter.0 (1111) ADD NEW DATA (48 + NEW 4)
                                2024-06-10 20:29:39.243 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe100000000000000800006606000000" -> null
                                2024-06-10 20:29:39.245 - debug: smartmeter.0 (1111) ADD NEW DATA (52 + NEW 4)
                                2024-06-10 20:29:39.246 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe00" -> null
                                2024-06-10 20:29:39.249 - debug: smartmeter.0 (1111) ADD NEW DATA (56 + NEW 4)
                                2024-06-10 20:29:39.250 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe0000401c00" -> null
                                2024-06-10 20:29:39.252 - debug: smartmeter.0 (1111) ADD NEW DATA (60 + NEW 3)
                                2024-06-10 20:29:39.253 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe0000401c00fe1000" -> null
                                2024-06-10 20:29:39.256 - debug: smartmeter.0 (1111) ADD NEW DATA (63 + NEW 3)
                                2024-06-10 20:29:39.256 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe0000401c00fe1000000000" -> null
                                2024-06-10 20:29:39.259 - debug: smartmeter.0 (1111) ADD NEW DATA (66 + NEW 4)
                                2024-06-10 20:29:39.259 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe0000401c00fe10000000000000001c" -> null
                                2024-06-10 20:29:39.261 - debug: smartmeter.0 (1111) ADD NEW DATA (70 + NEW 2)
                                2024-06-10 20:29:39.262 - debug: smartmeter.0 (1111) MATCH-RESULT MESSAGE: "060000000000fe0000401c00fe1000000000000200e60066060000000000fe0000401c00fe1000000000000008000066060000000000fe0000401c00fe10000000000000001c0066" -> null
                                

                                Vielen lieben Dank
                                Florian

                                apollon77 T 2 Replies Last reply Reply Quote 0
                                • apollon77
                                  apollon77 @k3flo last edited by apollon77

                                  @k3flo Ixh kann nur soviel sagen ... das sind keine SML Daten die da kommen, ergo ... er findet nichts. Spontan gecheckt sieht die Konfig aber an sich korrekt aus ...

                                  1 Reply Last reply Reply Quote 0
                                  • T
                                    TT-Tom @k3flo last edited by TT-Tom

                                    @k3flo

                                    Kannst du mal deine Einstellungen (Tasmota) aus dem Lesekopf zeigen. Interessant wäre das Script und die Ausgabe der Konsole, wenn du den Befehl eingegeben hast.

                                    sorry verwechselt, aber Prüfe mal deine Ausrichtung des Kopfes. prüfe auch mal die IR-Sendediode, ob diese noch hell leuchtet. Wenn diese altersschwach wird, kann es auch zu solchen Fehlern kommen.

                                    Homoran 1 Reply Last reply Reply Quote 0
                                    • Homoran
                                      Homoran Global Moderator Administrators @TT-Tom last edited by

                                      @tt-tom sagte in Adapter "smartmeter":

                                      Kannst du mal deine Einstellungen (Tasmota) aus dem Lesekopf zeigen

                                      ääähm

                                      @k3flo sagte in Adapter "smartmeter":

                                      Hichi USB

                                      sollte kein Tasmota haben

                                      T 1 Reply Last reply Reply Quote 1
                                      • T
                                        TT-Tom @Homoran last edited by TT-Tom

                                        @homoran

                                        jetzt wo du es schreibst, hast recht, habe ich verwechselt mit meinem Wärmezahler, der hängt per USB-Kopf am ioBroker. Nehme mein Eintrag zurück

                                        F 1 Reply Last reply Reply Quote 0
                                        • F
                                          final @TT-Tom last edited by

                                          Ich hab auch den gleichen Lesekopf, kann nachher mal in meine smartmeter settings schauen.
                                          Du hast aber anscheinend Redis am laufen? Das hab ich zumindest nicht.

                                          Zu den Daten vom Zähler, da hatte ich eine Anleitung vom Netzbetreiber bekommen bzw. runter geladen. Man konnte glaube ich auch auf einen erweiterten Datensatz in der Ausgabe umschalten am Zähler selber.

                                          Homoran 1 Reply Last reply Reply Quote 0
                                          • Homoran
                                            Homoran Global Moderator Administrators @final last edited by

                                            @final Es kommen ja Werte, die sehen nur nicht nach SML aus.

                                            Hab gerade auch diverse Anleitu gen von Netzbetreibern durchgeackert, da war in jeinem einzige eine Beschreibung der Info-Schnittstelle!

                                            Bei Volkszaehler.org habe ich auch nur den Hinweis auf SML gefunden.

                                            @k3flo
                                            bei welchem Netzbetreiber bist du?
                                            hast du von dem Informationen bekommen?

                                            k3flo 1 Reply Last reply Reply Quote 0
                                            • First post
                                              Last post

                                            Support us

                                            ioBroker
                                            Community Adapters
                                            Donate
                                            FAQ Cloud / IOT
                                            HowTo: Node.js-Update
                                            HowTo: Backup/Restore
                                            Downloads
                                            BLOG

                                            884
                                            Online

                                            31.6k
                                            Users

                                            79.4k
                                            Topics

                                            1.3m
                                            Posts

                                            281
                                            3635
                                            1699420
                                            Loading More Posts
                                            • Oldest to Newest
                                            • Newest to Oldest
                                            • Most Votes
                                            Reply
                                            • Reply as topic
                                            Log in to reply
                                            Community
                                            Impressum | Datenschutz-Bestimmungen | Nutzungsbedingungen
                                            The ioBroker Community 2014-2023
                                            logo