    Aufruf Sammlung an Modbus Anbindungen

    This topic has been deleted. Only users with topic management privileges can see it.
    • Sascha Roth
      Sascha Roth last edited by

      Orno LCD Digitaler Wechselstromzähler
      OR-WE-515

      Screenshot 2022-12-14 at 15-49-30 instances - ioBroker-Master.png Screenshot 2022-12-14 at 15-49-38 instances - ioBroker-Master.png Screenshot 2022-12-14 at 15-49-45 instances - ioBroker-Master.png

      Holding Register

      _address	deviceId	name	description	unit	type	len	factor	offset	formula	role	room	poll	wp	cw	isScale
      272	4	parameter.ID	Modbus Adresse		uint8be	1	1				enum.rooms.enum_1	true	false	false	false
      273	4	parameter.Baud	Baut Rate  = 1 > 1200 / 2 > 2400 / 3 > 4800 / 4 > 9600		uint8be	1	1				enum.rooms.enum_1	true	false	false	false
      274	4	parameter.display.1				1	1				enum.rooms.enum_1	true	false	false	false
      275	4	parameter.display.2				1	1				enum.rooms.enum_1	true	false	false	false
      276	4	parameter.display.3				1	1				enum.rooms.enum_1	true	false	false	false
      304	4	F	Frequenz	Hz	uint16be	1	0.01				enum.rooms.enum_1	true	false		
      305	4	U	Spannung	V	uint16be	1	0.01				enum.rooms.enum_1	true	false		
      313	4	I	Strom	A	uint32be	2	0.001				enum.rooms.enum_1	true	false	false	false
      320	4	P	Wirkleistung	W	uint32be	2	1	0			enum.rooms.enum_1	true	false		
      328	4	Q	Blindleistung 	var	uint32be	2	1				enum.rooms.enum_1	true	false	false	false
      336	4	S	Scheinleistung	VA	uint32be	2	1				enum.rooms.enum_1	true	false	false	false
      344	4	cos_phi	Leistungsfaktor		int16be	1	0.001				enum.rooms.enum_1	true	false	false	false
      40960	4	W	Wirkarbeit	kwh	uint32be	2	0.01				enum.rooms.enum_1	true	false		
      40990	4	Wq	Blindarbeit	kvarh	uint32be	2	1				enum.rooms.enum_1	true	false	false	false
      
      1 Reply Last reply Reply Quote 1
      • S
        Schello805 last edited by

        Ich habe hier beschrieben, wie ich unsere Pelletheizung von Solarfocus per Modbus Adapter in Homematic integriert habe. Ob das so richtig ist, weiß ich nicht, aber es funktioniert 🙂

        https://www.homematicblog.de/modbus-in-homematic/

        TheBam 1 Reply Last reply Reply Quote 0
        • TheBam
          TheBam @Schello805 last edited by

          @schello805
          Danke sieht gut aus. Kannst du evtl. Einen Export der Eingangsregister Posten?

          1 Reply Last reply Reply Quote 0
          • V
            V8Turbo @TheBam last edited by

            Gibt es etwas für Sofar Solar HYD 10 KTL WR ? Ich finde nur HEX Werte, wie kann man die eingeben ??

            wendy2702 1 Reply Last reply Reply Quote 0
            • wendy2702
              wendy2702 @V8Turbo last edited by

              @v8turbo HEX to Dec umrechnen mal versucht ?

              1 Reply Last reply Reply Quote 0
              • wendy2702
                wendy2702 last edited by

                Waterkotte EcoTouch Ai1 Geo 5008.5

                Auslesen:

                _address	name	description	unit	type	len	factor	offset	formula	role	room	cw	isScale
                1	Außentemperatur		°C	int16be	1	0.1	0		value		false	false
                2	Außentemperatur 1h Durchschnitt		°C	int16be	1	0.1	0		value		false	false
                3	Außentemperatur 24h Durchschnitt		°C	int16be	1	0.1	0		value		false	false
                4	Quelle ein		°C	int16be	1	0.1	0		value		false	false
                5	Quelle aus		°C	int16be	1	0.1	0		value		false	false
                6	Temperatur Verdampfer		°C	int16be	1	0.1	0		value		false	false
                7	Sauggastemperatur		°C	int16be	1	0.1	0		value		false	false
                8	Verdampfungsdruck		bar	int16be	1	0.1	0		value		false	false
                9	Druckgastemperatur	???	°C	int16be	1	0.1	0		value		false	false
                10	Rücklauf Soll		°C	int16be	1	0.1	0		value		false	false
                11	Rücklauf HZ		°C	int16be	1	0.1	0		value		false	false
                12	Vorlauf HZ		°C	int16be	1	0.1	0		value		false	false
                13	Temperatur Verflüssiger		°C	int16be	1	0.1	0		value		false	false
                15	Kondensationsdruck	???	bar	int16be	1	0.1	0		value		false	false
                17	Raumtemperatur_Abluft_KWL		°C	int16be	1	0.1	0		value		false	false
                18	Raumtemperatur_1_Stunde_Durchschnitt		°C	int16be	1	0.1	0		value		false	false
                19	Wasserspeicher Temperatur		°C	int16be	1	0.1	0		value		false	false
                23	Expansionsventil		%	int16be	1	0.1	0		value		false	false
                25	Verdichter Leistungsaufnahme		kW	int16be	1	0.1	0		value		false	false
                26	Thermische Energie		kw	int16be	1	0.1	0		value		false	false
                28	COP Waerme			int16be	1	0.1	0		value		false	false
                29	COP Kälte			int16be	1	0.1	0		value		false	false
                30	Heizung Ist		°C	int16be	1	0.1	0		value		false	false
                31	Heizung Soll		°C	int16be	1	0.1	0		value		false	false
                33	Kühlung Ist		°C	int16be	1	0.1	0		value		false	false
                34	Kühlung Soll		°C	int16be	1	0.1	0		value		false	false
                37	Warmwasser Soll		°C	int16be	1	0.1	0		value		false	false
                51	Heizkreispumpe Leistung		%	int16be	1	0.1	0		value		false	false
                52	Quellenpumpe_Leistung		%	int16be	1	0.1	0		value		false	false
                58	Leistung Kompressor %		%	int16be	1	0.1	0		value		false	false
                418	Energie_Verdichter_aktueller_Monat			int16be	1	0.1	0		value		false	false
                420	Energie_Quellenpumpe_aktueller_Monat			int16be	1	0.1	0		value		false	false
                435	Arbeitszahl_Gesamtsystem			int16be	1	0.1	0		value		false	false
                461	Arbeitszahl_Aktuelles_Jahr			int16be	1	0.1	0		value		false	false
                682	Sollwerterhöhung Heizkreis PV			int16be	1	0.1	0		value		false	false
                683	Sollwerterhöhung Kühlung PV			int16be	1	0.1	0		value		false	false
                684	Sollwerterhöhung Warmwasser PV			int16be	1	0.1	0		value		false	false
                818	Elektrische_Energie_Gesamt_Januar		kWh	int16be	1	0.1	0		value		false	false
                819	Elektrische_Energie_Gesamt_Februar		kWh	int16be	1	0.1	0		value		false	false
                820	Elektrische_Energie_Gesamt_März		kWh	int16be	1	0.1	0		value		false	false
                821	Elektrische_Energie_Gesamt_April		kWh	int16be	1	0.1	0		value		false	false
                822	Elektrische_Energie_Gesamt_Mai		kWh	int16be	1	0.1	0		value		false	false
                823	Elektrische_Energie_Gesamt_Juni		kWh	int16be	1	0.1	0		value		false	false
                824	Elektrische_Energie_Gesamt_Juli		kWh	int16be	1	0.1	0		value		false	false
                825	Elektrische_Energie_Gesamt_August		kWh	int16be	1	0.1	0		value		false	false
                826	Elektrische_Energie_Gesamt_September		kWh	int16be	1	0.1	0		value		false	false
                827	Elektrische Leistung Gesamt Oktober		kWh	int16be	1	0.1	0		value		false	false
                827	Elektrische_Energie_Gesamt_Oktober		kWh	int16be	1	0.1	0		value		false	false
                828	Elektrische_Energie_Gesamt_November		kWh	int16be	1	0.1	0		value		false	false
                829	Elektrische_Energie_Gesamt_Dezember		kWh	int16be	1	0.1	0		value		false	false
                830	Thermische_Leistung_Heizung_Januar		kWh	int16be	1	0.1	0		value		false	false
                831	Thermische_Leistung_Heizung_Februar		kWh	int16be	1	0.1	0		value		false	false
                832	Thermische_Leistung_Heizung_März		kWh	int16be	1	0.1	0		value		false	false
                833	Thermische_Leistung_Heizung_April		kWh	int16be	1	0.1	0		value		false	false
                834	Thermische_Leistung_Heizung_Mai		kWh	int16be	1	0.1	0		value		false	false
                835	Thermische_Leistung_Heizung_Juni		kWh	int16be	1	0.1	0		value		false	false
                836	Thermische_Leistung_Heizung_Juli		kWh	int16be	1	0.1	0		value		false	false
                837	Thermische_Leistung_Heizung_August		kWh	int16be	1	0.1	0		value		false	false
                838	Thermische_Leistung_Heizung_September		kWh	int16be	1	0.1	0		value		false	false
                839	Thermische_Leistung_Heizung_Oktober		kWh	int16be	1	0.1	0		value		false	false
                840	Thermische_Leistung_Heizung_November		kWh	int16be	1	0.1	0		value		false	false
                841	Thermische_Leistung_Heizung_Dezember		kWh	int16be	1	0.1	0		value		false	false
                842	Thermische_Leistung_Warmwasser_Januar		kWh	int16be	1	0.1	0		value		false	false
                843	Thermische_Leistung_Warmwasser_Februar		kWh	int16be	1	0.1	0		value		false	false
                844	Thermische_Leistung_Warmwasser_März		kWh	int16be	1	0.1	0		value		false	false
                845	Thermische_Leistung_Warmwasser_April		kWh	int16be	1	0.1	0		value		false	false
                846	Thermische_Leistung_Warmwasser_Mai		kWh	int16be	1	0.1	0		value		false	false
                847	Thermische_Leistung_Warmwasser_Juni		kWh	int16be	1	0.1	0		value		false	false
                848	Thermische_Leistung_Warmwasser_Juli		kWh	int16be	1	0.1	0		value		false	false
                849	Thermische_Leistung_Warmwasser_August		kWh	int16be	1	0.1	0		value		false	false
                850	Thermische_Leistung_Warmwasser_September		kWh	int16be	1	0.1	0		value		false	false
                851	Thermische_Leistung_Warmwasser_Oktober		kWh	int16be	1	0.1	0		value		false	false
                852	Thermische_Leistung_Warmwasser_November		kWh	int16be	1	0.1	0		value		false	false
                853	Thermische_Leistung_Warmwasser_Dezember		kWh	int16be	1	0.1	0		value		false	false
                878	Thermische_Leistung_Gesamt_Januar		kWh	int16be	1	0.1	0		value		false	false
                879	Thermische_Leistung_Gesamt_Februar		kWh	int16be	1	0.1	0		value		false	false
                880	Thermische_Leistung_Gesamt_März		kWh	int16be	1	0.1	0		value		false	false
                881	Thermische_Leistung_Gesamt_April		kWh	int16be	1	0.1	0		value		false	false
                882	Thermische_Leistung_Gesamt_Mai		kWh	int16be	1	0.1	0		value		false	false
                883	Thermische_Leistung_Gesamt_Juni		kWh	int16be	1	0.1	0		value		false	false
                884	Thermische_Leistung_Gesamt_Juli		kWh	int16be	1	0.1	0		value		false	false
                885	Thermische_Leistung_Gesamt_August		kWh	int16be	1	0.1	0		value		false	false
                886	Thermische_Leistung_Gesamt_September		kWh	int16be	1	0.1	0		value		false	false
                887	Thermische_Leistung_Gesamt_Oktober		kWh	int16be	1	0.1	0		value		false	false
                888	Thermische_Leistung_Gesamt_November		kWh	int16be	1	0.1	0		value		false	false
                889	Thermische_Leistung_Gesamt_Dezember		kWh	int16be	1	0.1	0		value		false	false
                924	COP_Gesamt_Januar			int16be	1	0.1	0		value		false	false
                925	COP_Gesamt_Februar			int16be	1	0.1	0		value		false	false
                926	COP_Gesamt_März			int16be	1	0.1	0		value		false	false
                927	COP_Gesamt_April			int16be	1	0.1	0		value		false	false
                928	COP_Gesamt_Mai			int16be	1	0.1	0		value		false	false
                929	COP_Gesamt_Juni			int16be	1	0.1	0		value		false	false
                930	COP_Gesamt_Juli			int16be	1	0.1	0		value		false	false
                931	COP_Gesamt_August			int16be	1	0.1	0		value		false	false
                932	COP_Gesamt_September			int16be	1	0.1	0		value		false	false
                933	COP_Gesamt_Oktober			int16be	1	0.1	0		value		false	false
                934	COP_Gesamt_November			int16be	1	0.1	0		value		false	false
                935	COP_Gesamt_Dezember			int16be	1	0.1	0		value		false	false
                5006	Aktueller_Tag			int16be	1	1	0		value		false	false
                5007	Aktueller_Monat			int16be	1	1	0		value		false	false
                5008	Aktuelles_Jahr			int16be	1	1	0		value		false	false
                5009	Aktuelle_Stunde			int16be	1	1	0		value		false	false
                5010	Aktuelle_Minute			int16be	1	1	0		value		false	false
                5011	Betriebsstunden_Verdichter		h	int16be	1	1	0		value		false	false
                5019	Betriebsstunden_Heizungsumwälzpumpe		h	int16be	1	1	0		value		false	false
                5021	Betriebsstunden_Quellenpumpe		h	int16be	1	1	0		value		false	false
                5052	Zustand_WP			int16be	1	1	0		value		false	false
                

                ändern WW Temp:

                _address	name	description	unit	type	len	factor	offset	formula	role	room	poll	wp	cw	isScale
                38	Wassertemperatur Soll		°C	uint16be	1	1	0		level		true			
                

                Wenn man z.B. Eine WW-Temp von 55 Grad einstellen muss man das Register mit "550" beschreiben. Zumindest ist das bei mir so.

                F E P 3 Replies Last reply Reply Quote 1
                • M
                  MartyBr last edited by

                  Kostal Smart Energy Meter:

                  _address	name	description	unit	type	len	factor	offset	formula	role	room	poll	wp	cw	isScale
                  0	Summe_Leistung_Netzbezug	Wirkleistung (Netzbezug)	W	uint32be	2	1	0		value		true			
                  2	Summe_Leistung_Einspeisung	Wirkleistung (Einspeisung)	W	uint32be	2	1	0		value		true			
                  4	Summe_Blindleistung_Netzbezug	Blindleistung (Netzbezug)	W	uint32be	2	1	0		value		true			
                  6	Summe_Blindleistung_Einspeisung	Blindleistung (Einspeisung)	W	uint32be	2	1	0		value		true			
                  16	Summe_Scheinleistung_Netzbezug	Scheinleistung (Netzbezug)	W	uint32be	2	1	0		value		true			
                  18	Summe_Scheinleistung_Einspeisung	Scheinleistung (Einspeisung)	W	uint32be	2	1	0		value		true			
                  40004	Hersteller	Hersteller		string	2	1	0		value		true			
                  40020	Name	Name		string	2	1	0		value		true			
                  40052	Seriennummer	Seriennummer		string	2	1	0		value		true			
                  40071	M_AC_Current	AC Current (sum of active phases)	A	int16be	1	1	0		value		true			
                  40072	M_AC_Current_A	Phase A AC current	A	int16be	1	1	0		value		true			
                  40073	M_AC_Current_B	Phase B AC current	A	int16be	1	1	0		value		true			
                  40074	M_AC_Current_C	Phase C AC current	A	int16be	1	1	0		value		true			
                  40075	M_AC_Current_SF	AC Current Scale Factor		int16be	1	1	0		value		true			
                  40076	M_AC_Voltage_LN	Line to Neutral AC Voltage (average of active phases)	V	int16be	1	1	0		value		true			
                  40077	M_AC_Voltage_LA	Phase A to Neutral AC Voltage	V	int16be	1	1	0		value		true			
                  40078	M_AC_Voltage_LB	Phase B to Neutral AC Voltage	V	int16be	1	1	0		value		true			
                  40079	M_AC_Voltage_CN	Phase C to Neutral AC Voltage	V	int16be	1	1	0		value		true			
                  40080	M_AC_Voltage_LL	Line to Line AC Voltage (average of active phases)	V	int16be	1	1	0		value		true			
                  40081	M_AC_Voltage_AB	Phase A to Phase B AC Voltage	V	int16be	1	1	0		value		true			
                  40082	M_AC_Voltage_BC	Phase B to Phase C AC Voltage	V	int16be	1	1	0		value		true			
                  40083	M_AC_Voltage_CA	Phase C to Phase A AC Voltage	V	int16be	1	1	0		value		true			
                  40084	M_AC_Voltage_SF	AC Voltage Scale Factor		int16be	1	1	0		value		true			
                  40085	M_AC_Freq	AC Frequency	Hz	int16be	1	1	0		value		true			
                  40086	M_AC_Freq_SF	AC Frequency Scale Factor		int16be	1	1	0		value		true			
                  40087	M_AC_Power	Total Real Power (sum of active phases)	W	int16be	1	1	0		value		true			
                  40088	M_AC_Power_A	Phase A AC Real Power	W	int16be	1	1	0		value		true			
                  40089	M_AC_Power_B	Phase B AC Real Power	W	int16be	1	1	0		value		true			
                  40090	M_AC_Power_C	Phase C AC Real Power	W	int16be	1	1	0		value		true			
                  40091	M_AC_Power_SF	AC Real Power Scale Factor		int16be	1	1	0		value		true			
                  40092	M_AC_VA	Total AC Apparent Power (sum of active phases)	VA	int16be	1	1	0		value		true			
                  40093	M_AC_VA_A	Phase A AC Apparent Power	VA	int16be	1	1	0		value		true			
                  40094	M_AC_VA_B	Phase B AC Apparent Power	VA	int16be	1	1	0		value		true			
                  40095	M_AC_VA_C	Phase C AC Apparent Power	VA	int16be	1	1	0		value		true			
                  40096	M_AC_VA_SF	AC Apparent Power Scale Factor		int16be	1	1	0		value		true			
                  40097	M_AC_VAR	Total AC Reactive Power (sum of ac- tive phases)	var	int16be	1	1	0		value		true			
                  40098	M_AC_VAR_A	Phase A AC Reactive Power	var	int16be	1	1	0		value		true			
                  40099	M_AC_VAR_B	Phase B AC Reactive Power	var	int16be	1	1	0		value		true			
                  40100	M_AC_VAR_C	Phase C AC Reactive Power	var	int16be	1	1	0		value		true			
                  40101	M_AC_VAR_ SF	AC Reactive Power Scale Factor		int16be	1	1	0		value		true			
                  40102	M_AC_PF	Average Power Factor (average of active phases)	%	int16be	1	1	0		value		true			
                  40103	M_AC_PF_A	Phase A Power Factor	%	int16be	1	1	0		value		true			
                  40104	M_AC_PF_B	Phase B Power Factor	%	int16be	1	1	0		value		true			
                  40105	M_AC_PF_C	Phase C Power Factor	%	int16be	1	1	0		value		true			
                  40106	M_AC_PF_SF	AC Power Factor Scale Factor		int16be	1	1	0		value		true			
                  40107	M_Exported	Total Exported Real Energy	Wh	int32be	2	1	0		value		true			
                  40109	M_Exported_A	Phase A Exported Real Energy	Wh	int32be	2	1	0		value		true			
                  40111	M_Exported_B	Phase B Exported Real Energy	Wh	int32be	2	1	0		value		true			
                  40113	M_Exported_C	Phase C Exported Real Energy	Wh	int32be	2	1	0		value		true			
                  40115	M_Imported	Total Imported Real Energy	Wh	int32be	2	1	0		value		true			
                  40117	M_Imported_A	Phase A Imported Real Energy	Wh	int32be	2	1	0		value		true			
                  40119	M_Imported_B	Phase B Imported Real Energy	Wh	int32be	2	1	0		value		true			
                  40121	M_Imported_C	Phase C Imported Real Energy	Wh	uint32sw	2	1	0		value		true			
                  40123	M_Energy_W_SF	Real Energy Scale Factor3		int16be	1	1	0		value		true			
                  40124	M_Exported_VA	Total Exported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40126	M_Exported_VA_A	Phase A Exported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40128	M_Exported_VA_B	Phase B Exported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40130	M_Exported_VA_C	Phase C Exported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40132	M_Imported_VA	Total Imported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40134	M_Imported_VA_A	Phase A Imported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40136	M_Imported_VA_B	Phase B Imported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40138	M_Imported_VA_C	Phase C Imported Apparent Energy	VAh	int32be	2	1	0		value		true			
                  40140	M_Energy_VA_SF	Apparent Energy Scale Factor		int16be	1	1	0		value		true			
                  40141	M_Import_VARh_Q1	Quadrant 1: Tota Imported Reactive Energy	VARh	int32be	2	1	0		value		true			
                  40143	M_Import_VARh_Q1A	Phase A – Quadrant 1: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40145	M_Import_VARh_Q1B	Phase B – Quadrant 1: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40147	M_Import_VARh_Q1C	Phase C – Quadrant 1: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40149	M_Import_VARh_Q2	Quadrant 2: Total Imported Reactive Energy	VARh	int32be	2	1	0		value		true			
                  40151	M_Import_VARh_Q2A	Phase A – Quadrant 2: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40153	M_Import_VARh_Q2B	Phase B – Quadrant 2: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40155	M_Import_VARh_Q2C	Phase C – Quadrant 2: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40157	M_Export_VARh_Q3	Quadrant 3: Total Imported Reactive Energy	VARh	int32be	2	1	0		value		true			
                  40159	M_Export_VARh_Q3A	Phase A – Quadrant 3: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40161	M_Export_VARh_Q3B	Phase B – Quadrant 3: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40163	M_Export_VARh_Q3C	Phase C – Quadrant 3: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40165	M_Export_VARh_Q4	Quadrant 4: Tota Imported Reactive Energy	VARh	int32be	2	1	0		value		true			
                  40167	M_Export_VARh_Q4A	Phase A – Quadrant 4: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40169	M_Export_VARh_Q4B	Phase B – Quadrant 4: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40171	M_Export_VARh_Q4C	Phase C – Quadrant 4: Imported Reac- tive Energy	VARh	int32be	2	1	0		value		true			
                  40173	M_Energy_VAR_SF	Reactive Energy Scale Factor		int16be	1	1	0		value		true			
                  40174	M_Events	Event flags		int32be	2	1	0		value		true			
                  
                  1 Reply Last reply Reply Quote 0
                  • F
                    Flauschi @wendy2702 last edited by

                    @wendy2702 was noch cool wäre, wenn man im Holdingregister die "Temperaturanpassung" setzen könnte...
                    glaub da such ich als nächstes mal:

                    83394672-51c2-4910-9e4a-fbd82fdb76c3-image.png

                    wendy2702 1 Reply Last reply Reply Quote 0
                    • wendy2702
                      wendy2702 @Flauschi last edited by

                      @flauschi Du weisst nicht zufällig ob man die Raumtemperatur schreiben kann ?

                      apollon77 1 Reply Last reply Reply Quote 0
                      • apollon77
                        apollon77 @wendy2702 last edited by

                        @wendy2702 bitte funktionale Diskussionen in eigenen threads führen ;-). Danke

                        wendy2702 1 Reply Last reply Reply Quote 0
                        • wendy2702
                          wendy2702 @apollon77 last edited by

                          @apollon77 zur Kenntnis genommen.

                          1 Reply Last reply Reply Quote 0
                          • E
                            Eaterhnk @wendy2702 last edited by

                            @wendy2702 nutzt du die zusätzliche Modbuskarte von Waterkotte? Ich habe gelesen, dass das Auslesen von Daten wohl auch ohne diese Karte funktionieren soll. Krieg die Verbindung aber nicht hin. Mein Adapter bleibt auf rot, liegt aber auch vielleicht an den Einstellungen. Kannst du deine vielleicht noch hier reinsetzen?

                            wendy2702 1 Reply Last reply Reply Quote 0
                            • wendy2702
                              wendy2702 @Eaterhnk last edited by

                              @eaterhnk sagte in Aufruf Sammlung an Modbus Anbindungen:

                              nutzt du die zusätzliche Modbuskarte von Waterkotte? Ich habe gelesen, dass das Auslesen von Daten wohl auch ohne diese Karte funktionieren soll. Krieg die Verbindung aber nicht hin

                              OK. Wurde mir seitens Waterkotte anders erzählt aber möglich ist ja alles.

                              205c36ec-bb47-420b-9f49-850a244d7aa1-grafik.png
                              2ce6877e-1dc5-4934-b6c2-d48c2c5a24ee-grafik.png

                              E 1 Reply Last reply Reply Quote 0
                              • E
                                Eaterhnk @wendy2702 last edited by

                                @wendy2702 Danke dir, scheint aber eine Fehlinformation gewesen zu sein. Hatte es FHEM oder Loxone Forum gelesen bleibt aber weiterhin rot.

                                wendy2702 1 Reply Last reply Reply Quote 0
                                • wendy2702
                                  wendy2702 @Eaterhnk last edited by

                                  @eaterhnk sagte in Aufruf Sammlung an Modbus Anbindungen:

                                  @wendy2702 Danke dir, scheint aber eine Fehlinformation gewesen zu sein. Hatte es FHEM oder Loxone Forum gelesen bleibt aber weiterhin rot.

                                  OK. Siehe Chat da es hier nicht hin gehört

                                  1 Reply Last reply Reply Quote 0
                                  • M
                                    mane444 last edited by

                                    Hi hab einen ACTHOR9s verbaut. Ich lese die Daten aus und gebe die Bezugsleistung vom Iobroker vor.

                                    Das ganze hab ich mit zwei Modbus Instanzen gelöst.
                                    Hier die Einstellungen:
                                    zur Übersicht:
                                    IP IOB 192.168.2.220
                                    ACTHOR 192.168.2.192

                                    1. Modbus Instanz Daten auslesen:
                                      Einstellungen:
                                      6ac4347b-b8ff-4236-a9b7-826ce475b0e0-image.png
                                      9a131bbb-1be2-41f7-8e3d-97a8bd2325fe-image.png
                                      Holding Register:
                                      R_Holding_Register.txt

                                    2. Modbus Instanz ACTHOR Bezugs-Leistung vorgeben:
                                      Einstellungen:
                                      6cb84315-bd06-4e06-8dd0-f88d48bd2089-image.png
                                      6390ef5d-3952-47fe-8433-cf4c7fd9e1e9-image.png
                                      Holding Register:
                                      W_Holding_Register.txt

                                    MyPV ACTHOR9S
                                    E/Ethernet Version: a0020900  
                                    P/Leistungsteil Version: 110  
                                    S/Leistungsteil 9s Version: 102

                                    Einstellungen am ACTHOR:
                                    6bbbea87-7744-4b34-a599-8f3a9f5a596c-image.png
                                    4d2fd408-abec-4e17-b12e-c7e2a483f750-image.png

                                    1 Reply Last reply Reply Quote 0
                                    • P
                                      PEPITO82 @wendy2702 last edited by

                                      @wendy2702 Vielen Dank fürs Teilen. Hast Du es mittlerweile vielleicht auch noch hinbekommen, dass man beim Setzen der Solltemperatur den tatsächlichen Temperaturwert angibt statt mit einer zusätzlichen 0?

                                      Ich nutze auch noch diese Register:
                                      5030 --> Heizen Handabschaltung
                                      5032 --> Warmwasser Handabschaltung
                                      6270 --> Schalter Heizungspumpe

                                      Ggf. sind die für Dich auch noch interessant.

                                      M wendy2702 2 Replies Last reply Reply Quote 0
                                      • M
                                        mane444 @PEPITO82 last edited by

                                        @pepito82 Ich kenn das so nicht.
                                        Ich gebe im Register 1002 die Temperatur vor, und die kommt so auch beim ACTHOR an.
                                        35a01e72-e89b-47c8-9cbd-cc709f85d091-image.png 90a4864d-68d5-475a-b4f9-d8dfdd0589b1-image.png
                                        Hast du den Faktor richtig gesetzt ?
                                        6b576a00-d36a-40f3-864c-a27cf7c1a5ff-image.png

                                        P 1 Reply Last reply Reply Quote 1
                                        • P
                                          PEPITO82 @mane444 last edited by

                                          @mane444 Danke. Ich hatte mit einer Formel gearbeitet. Mit Faktor funktioniert es einwandfrei.

                                          1 Reply Last reply Reply Quote 0
                                          • wendy2702
                                            wendy2702 @PEPITO82 last edited by

                                            @pepito82 sagte in Aufruf Sammlung an Modbus Anbindungen:

                                            @wendy2702 Vielen Dank fürs Teilen. Hast Du es mittlerweile vielleicht auch noch hinbekommen, dass man beim Setzen der Solltemperatur den tatsächlichen Temperaturwert angibt statt mit einer zusätzlichen 0?

                                            Ich nutze auch noch diese Register:
                                            5030 --> Heizen Handabschaltung
                                            5032 --> Warmwasser Handabschaltung
                                            6270 --> Schalter Heizungspumpe

                                            Ggf. sind die für Dich auch noch interessant.

                                            Wegen der zusätzlichen "0" wurde ja gelöst, wobei mir das persönlich egal ist ob das Script 55 oder 550 schreibt.

                                            Kannst du den Export der anderen Register bereitstellen?

                                            1 Reply Last reply Reply Quote 0
                                            • First post
                                              Last post

                                            Support us

                                            ioBroker
                                            Community Adapters
                                            Donate

                                            806
                                            Online

                                            31.7k
                                            Users

                                            79.8k
                                            Topics

                                            1.3m
                                            Posts

                                            geräte modbus sammlung
                                            31
                                            66
                                            13187
                                            Loading More Posts
                                            • Oldest to Newest
                                            • Newest to Oldest
                                            • Most Votes
                                            Reply
                                            • Reply as topic
                                            Log in to reply
                                            Community
                                            Impressum | Datenschutz-Bestimmungen | Nutzungsbedingungen
                                            The ioBroker Community 2014-2023
                                            logo